PowerWalker VFI 1500 LICR IoT — Modbus TCP register map

192.168.1.141:502, function code 3, unit id ignored (1, 2, 3 and 255 all answer identically). Reads only — do not write, these are live UPS settings.

PowerWalker does not publish the map; the manual says to "contact your service for protocol details". Everything below was derived by reading registers while comparing against the front-panel LCD, so each entry is confirmed against a displayed value rather than inferred.

Identity (static, ASCII, big-endian per register)

Registers Value
0–4 PHOENIXTEC (Eaton subsidiary; OEM behind PowerWalker)
16–24 VFI 1500 LICR IoT
48–53 00.03.1760 — UPS firmware
56–63 CPANR1398610001 — serial
286–290 01.08.000 — network stack version
296–299 4aebc90e — device id

Telemetry

Reg Metric Scale Verified against LCD
128 temperature ÷10 °C 25.2–25.4 vs 25.4 °C
129 input frequency ÷10 Hz 50.0 Hz
132 input voltage ÷10 V 232.7 vs 232 V
144 output frequency ÷10 Hz 50.0 Hz
147 output voltage ÷10 V 230.3 vs 230 V
153 output current ÷10 A 1.1–1.4 vs 1.1–1.3 A
162 load % 17–21 vs 17–21 %
165 runtime left min 57–78 vs 66–79 min
169 battery charge % 100 %
170 battery voltage ÷10 V 52.7 V (48 V string, charging)
176 bypass voltage ÷10 V tracks input
250 nominal output V ÷10 V 230.0 V

0xFFFF means "not applicable" — the three-phase registers read that way on this single-phase unit.

Apparent power is not exposed; derive it as (147/10) * (153/10), which gives ~287 VA against the 280–300 VA the panel showed. Real power would additionally need the power factor, which is also absent.

Still unidentified: 153's neighbours 156 (1–2) and 159 (2–3), and 166, which swings 0–45 with no obvious correlation.

Enabling it

Modbus TCP is off by default. Enable it from the front panel; until then port 502 accepts the TCP connection but returns zero bytes, which looks exactly like a hung service. The "IoT" (cloud) feature is separate and can stay off.

SNMP is not listening — no reply to v2c public on udp/161. The intelligent card slot is empty; this is the UPS's built-in Ethernet port, so there is no NMC to reset.